| Input | |
| Voltage | 400 Vac | 
| Tolerance | 320 – 450V | 
| Frequency | 50Hz ± 6% | 
| Output | |
| Voltage | 400Vac ± 1% | 
| Power Factor | 0.8 | 
| Transfer Time | 0 ms | 
| Frequency | 50Hz ± 6% (On Mains) | 
| 50Hz ± 0.5% (On Battery) | |
| Waveform | Pure Sine Wave | 
| THDi | Linear Load ≤ 3%; Non-linear Load ≤ 5% | 
| Crest Factor | 3 : 1 (Max) | 
| Bypass Facility | Maintenance Bypass and Static Bypass | 
| DC Bus / DC Functions: | |
| DC Bus Voltage | 384V | 
| Charging Current | 5 – 20A, Adjustable | 
| Cold-Start Function | Yes | 
| Battery Charging in OFF Mode | Yes | 
| Battery Type | Sealed, Maintenance-free VRLA | 
| LCD User Interface: | |
| Metering / Indications for | Voltage | 
| Load % | |
| Frequency | |
| General Status | |
| Alarm | |
| Communication: | |
| Interfaces | RS232 | 
| Overload | |
| 105~125% | 10 mins (Output swithes to bypass after 60s) | 
| >130% | 1 min | 
| Environment: | |
| Temperature | 0 ~ 40oC | 
| Humidity | 20 ~ 90% Non-condensing | 
| Altitude | < 1000m | 
| IP Class | 20 | 
| Physical: | |
| Dimensions (mm) | 10-20kVA : 560 x 700 x 1040 (W x D x H) | 
| 30-40kVA : 660 x 800 x 1380 (W x D x H) | |
| 60-80kVA : 1540 x 880 x 1570 (W x D x H) | |
| 100-200kVA : 2000 x 980 x 1800 (W x D x H) | |
| Weight (Kg) | 10kVA : 260kg | 
| 15kVA : 350kg | |
| 20kVA : 400kg | |
| 30kVA : 480kg | |
| 40kVA : 650kg | |
| 60kVA : 650kg | |
| 80kVA : 1200kg | |
| 100kVA : 1330kg | |
| 120-200kVA : On Request | |
		UPS, Vectronic Ups
					 
	
	
			60kVA Vectronic Online UPS (with batteries)
 
	Description:
Profie:          Tower
Range:         60kVA
Voltage:        400Vac
Frequency:   50Hz